High temperature resistance and good durability; Safe and non-toxic
Low viscosity, conducive to liquid transportation and heat conduction
High safety and high flash point
Extremely wide range of use, no need to replace the thermal medium during heat conduction and cooling
Low temperature resistance, maintaining low viscosity even at -50 degrees Celsius
Extremely low dielectric constant, good insulation performance
Application method
As a thermal conductive medium used in closed loop systems, such as heat exchangers and jacketed loop systems
As a thermal conductive medium in direct contact with the working interface, such as as as an immersion coolant
Transportation and storage conditions
Transport at room temperature and not exceeding 45 degrees Celsius
Store in a well ventilated and cool place
Avoid light when storing for a long time
Other precautions
The phase change thermal conductivity series should pay attention to the matching of cooling system power during high-power thermal conductivity, otherwise the phase change material may be affected by pressure
Loss due to fluctuations in force.
Not mixed with other heat transfer oils for use
When directly contacting live parts, please avoid contact with water
Avoid contact with other corrosive liquids and metals
Avoid direct contact with the skin
Please be aware of the risk of suffocation when using under sealed conditions
| indicator | unit | data | Testing basis |
| appearance | / | Colorless to pale yellow transparent | visual estimation |
| Viscosity 25 ° C | mm²/s | 10 Shi 1 | GB/T 265 |
| Viscosity 40 ° C | mm²/s | 8±1 | GB/T 265 |
| refractive index | / | 1.39-1.41 | GB/T 6488 |
| Flash point (closed) | ℃ | >180 | GB/T 261 |
| density | g/cm² | 0.93 | GB/T 1884 |
| pour point | ℃ | ≤-50 | GB/T3535 |
| dielectric strength | KV | >50 | GB/T507 |
| dielectric constant | / | 2.6±0.1 | GB/T 5654 |
| Dielectric loss factor | / | ≤0.005 | GB/T 5654 |
| thermal conductivity | w/m.K | 0.14 | GB/T32064 |
| specific heat capacity | J/(g/℃) | 1.66 | GB/T 19466.4 |